Multi-Port Valve ​

A smart-object symbol for a 3-way or 4-way valve, showing which ports are currently connected.

In Studio ​

In Studio, double-click Multi-Port Valve in the Process category of the Components panel. It is added to the open view, where you can drag it into place.

When to use ​

Use Multi-Port Valve for a diverter or selector valve with more than two ports — a standard Valve's single-stem body cannot represent more than two connections.

Properties ​

PropertyTypeDefaultDescription
ValueString(none)The overall device state — same Closed/Open/Fault contract as Valve's Value, used for the whole-symbol paint on Fault or when there is no live data.
Flow PathString(none)Which ports are currently connected, as any text naming their port letters (e.g. AB, A,B, A/B all mean ports A and B are connected). A port named in Flow Path renders in the open color; every other port renders in the closed color. A value that names no known port renders every port closed, and an open valve with no named port is captioned NO PATH. A closed valve draws every port closed whatever Flow Path says.
Ports3, 43Number of ports: 3 (default) or 4.
Orientation (stem port)down, right, up, leftdownWhich way the stem port (C) points: down (as drawn, default), right, up, or left. The whole valve turns; the caption stays upright.
LabelStringValveThe caption shown below the symbol.
Show Captiontrue, falsetrueShows or hides the caption (the name and state word) under the symbol. Off also gives that height back to the drawing — use it when a separate label template sits beside the symbol.
Closed ColorColor#808080The color for a port not on the current flow path. Defaults to the HMI palette's stopped-state color.
Open ColorColor#FFFFFFThe color for a port on the current flow path. Defaults to the HMI palette's running-state color.
Fault ColorColor#E12D39The whole-symbol color on Fault. Defaults to the HMI palette's priority-1 alarm color.

Binding ​

Click Bind… on the Value property and bind it to a tag or an expression to drive the live value.

This binding is read-only — the component never writes to the tag.

Flow Path is a second, independent binding — see that field. Per-port coloring only applies while the overall state is Closed or Open; a Fault or no-data state paints the whole symbol instead of per-port, since neither state has a trustworthy flow path.